| Powerhouse Products - 800kW |
 |
 |
 |
 |
| Rating |
 |
| No-Break Capacity1: |
800 kW single output |
|
|
 |
 |
 |
 |
 |
 |
| Dimensions |
 |
| Height: |
9'6" /2896mm |
 |
 |
 |
 |
 |
 |
| Width: |
8' / 2438mm |
 |
 |
 |
 |
 |
 |
| Length: |
40' / 12192mm |
 |
 |
 |
 |
 |
 |
| Weight: |
37479 lbs / 17000kg |
|
|
 |
 |
 |
 |
 |
 |
| Electrical Entry |
 |
Side / bottom |
|
 |
 |
 |
|
 |
 |
 |
|
 |
| Electrical |
 |
 |
 |
 |
| Input |
 |
| Voltage: |
380/400/415 VAC 3-phase, 4 wire plus Ground |
 |
 |
 |
 |
 |
 |
| Voltage Range: |
+10%/-15% (programmable) +10% 380VAC |
 |
 |
 |
 |
 |
 |
| Frequency: |
50 Hz +/- 10% maximum (programmable) +/- 3% (default) |
 |
 |
 |
 |
 |
 |
| Power Factor: |
0.99 at rated load and nominal voltage |
 |
 |
 |
 |
 |
 |
| Surge Withstand: |
Meets IEEE 587/ANSI C62.41 |
 |
 |
 |
 |
 |
 |
| Generator Walk-in: |
1 to 15 seconds (programmable) |
 |
 |
 |
 |
 |
 |
| Harmonic Distortion: |
Linear Load <3% at 100% load |
 |
 |
 |
 |
 |
 |
| |
Non-Linear Load2 <5% at 100% load |
 |
 |
 |
 |
 |
 |
| Current-Nominal (380VAC): |
1684 |
 |
 |
 |
 |
 |
 |
| Current-Nominal (400 VAC): |
1600 |
 |
 |
 |
 |
 |
 |
| Current-Nominal (415 VAC): |
1542 |
 |
 |
 |
 |
 |
 |
| Current-Max Continuous: |
2000 |
 |
 |
 |
 |
 |
 |
| Current-Max Non-continuous: |
2080 |
|
|
 |
 |
 |
 |
 |
 |
| UPS Output |
 |
| Voltage |
380/400/415 VAC 3-phase, 4-wire plus Ground |
 |
 |
 |
 |
 |
 |
| Voltage Regulation |
Steady State +/- 1% for +/- 10% input |
 |
 |
 |
 |
 |
 |
| |
Flywheel Mode +/- 1% steady state |
 |
 |
 |
 |
 |
 |
| |
Transient +/- 1% within 50 mSec for 100% load step |
 |
 |
 |
 |
 |
 |
| Voltage Distortion2 |
<3% linear loads |
 |
 |
 |
 |
 |
 |
| |
<5% for 100% non-linear loads |
 |
 |
 |
 |
 |
 |
| Frequency |
50Hz (mains synchronised) |
 |
 |
 |
 |
 |
 |
| |
(normal operation +/- 0.2% free running) |
 |
 |
 |
 |
 |
 |
| Slew Rate |
Adjustable from 0.2Hz/second to 3.0Hz/second |
 |
 |
 |
 |
 |
 |
| Current-Nominal (380VAC) |
1521 |
 |
 |
 |
 |
 |
 |
| Current-Nominal (400 VAC) |
1445 |
 |
 |
 |
 |
 |
 |
| Current-Nominal (415 VAC) |
1393 |
 |
 |
 |
 |
 |
 |
| Short Circuit Capacity |
10 x input (mains connected) |
 |
 |
 |
 |
 |
 |
| |
Up to 10 x input (emergency operation) |
 |
 |
 |
 |
 |
 |
| Critical Power Efficiency3,4 |
98% |
|
|
 |
 |
 |
| Generator |
 |
 |
 |
 |
| |
 |
| Generator Size |
1000kW |
 |
 |
 |
 |
 |
 |
| Tank Capacity (litres) |
1500 |
 |
 |
 |
 |
 |
 |
| Autonomy @ 75% load (hours) |
6 |
|
|
 |
 |
 |
| Environmental |
 |
 |
 |
 |
| Noise/Protection |
 |
| Audible Noise |
85dB(A)@1 metre |
 |
 |
 |
 |
 |
 |
| Protection |
NEMA 2 / IP 12 |
|
|
 |
 |
 |
 |
 |
 |
| Temperature |
 |
| Operating |
14o to 104o F (-10o to 40o C) |
 |
 |
 |
 |
 |
 |
| Storage |
-13o to 158o F (-25o to 70o C) |
|
|
 |
 |
 |
 |
 |
 |
| Humidity |
 |
Up to 99% (non-condensing) |
|
 |
 |
 |
 |
 |
 |
| Altitude5 |
 |
Up to 3000’ (1000m) |
|
 |
 |
 |
 |
 |
 |
| Emissions and Immunity |
 |
EN 50091-2 |
|
 |
 |
 |
| 1 Load protected by uninterruptible power supply and generator |
| 2 EN59001-3 |
| 3 DC energy storage off-line |
| 4 Engine pre-heater off-line |
| 5 Please contact us for higher elevations |
 |
 |
 |